Product Description
Introduction
DGA2013-1 power system dedicated insulation oil and gas chromatograph runs by computer automatic control, all-keyboard operation and large-screen liquid crystal display according to the requirements of power system«dissolved gas component determination in insulation oil (chromatography)» ,and is characterized by high-precision temperature control, stable and reliable performance, high sensitivity, good reproducibility and so on.
The analyzer adopts double- pillar parallel shunt system ,equipped with TCD, double FID and methane conversion oven , and c ould achieve total analysis of nine components (H 2 ,O 2 ,N 2 ,CH 4 ,C 2 H 2 ,C 2 H 4 ,C 2 H 6 ,CO, CO 2 )of dissolved gas in insulation oil by one time.
The analyzer can be employ ed for internal fault detection of power system oil and gas equipment, cooling medium analysis of hydrogen-cooled generators, impurity analysis of sulfur hexafluoride, the boiler flue gas analysis, gas analysis and environmental monitoring analysis. Due to its employment not only for special analysis, but also for general analysis, the analyzer becomes the most effective gas analytical instrument in petroleum, chemical engineering, mining and other systems.
1. Technical parameters
1. 1 Temperature c ontrol
① Temperature range
Column chamber: r oom temperature+15 ℃ — 399 ℃
V aporizing chamber: r oom temperature+30 ℃ — 399 ℃
C onversion furnace : r oom temperature+30 ℃ — 399 ℃
T hermal conductivity detector: room temperature+30 ℃ — 399 ℃
H ydrogen flame detector : r oom temperature+30 ℃ — 399 ℃
② T emperature control precision: ±0.1 ℃
1. 2 T hermal conductivity detector
① Sensitivity: minimum detectable concentration of hydrogen≥5μl/L
② N oise: ≤0.05mv
③ D rift: ≤0.15mv/30min
1.3 H ydrogen flame detector
① M inimum detectable concentration of hydrocarbon≥5μl/L
② M inimum detectable concentration of CO 、 CO 2 ≥5μl/L
③ N oise: ≤0.05mv
④ D rift: ≤0.15mv/30min
1. 4 W hole machine s tart-up time: less than 3 hours
2. Features
2. 1 C omputer - keyboard operation
This realize s five heating zone temperature control, detector control, over-temperature protection, "zero" degree protection, air break protection and other functions, so as to protect the chromatographic column and thermal conductivity rhenium tungsten filament most effectively.
2. 2 L arge-screen liquid crystal display
It could display a large amount of information intuitively and clearly.
2. 3 Advanced chromatography process
Based on only one injection and three - detectors analytical process, the analyzer greatly increases detection sensitivity of hydrocarbon gas. Double hydrogen flame setting also reduce s the detection impact caused by the gas content differences.
3 . Working conditions
3. 1 N ormal instrument working conditions
① Environmental condition : 5 ℃ —35 ℃
② Relative Humidity : ≤80%
③ P ower supply : 220V±10% 50Hz±0.5Hz
④ 3KW power provided.
⑤ N o strong electromagnetic interference, corrosive gas and strong shock in the surroundings.
3. 2 G as source
① A ir purity: ensure the purity of carrier gas and hydrogen is more than 99.99%, the air to be used is purified and air generator function in dust, oil and water removal.
② O utput pressure of steel cylinder relief valve: nitrogen 0.35MPa, hydrogen 0.25MPa, air 0.35MPa
③ P lease replace steel cylinder timely when output pressure fell below 2MPa.
3. 3 Ground wire
To ensure personal safety and instrument performance, the instrument must be reliably linked to the land. It is suggested to bury the ground wire in the s oil 1 meter below.